How to install an earthing system step by step (electrodes, strip, measurement)

In short: An earthing system is installed by burying vertical electrodes (galvanised pipes/profiles of 1.5-3 m) at a minimum depth of 0.8 m, connected by an OL-Zn strip (usually 40x4 mm) through welding, over which salt and bentonite are added for low resistivity; after installation, the dispersion resistance is measured with a PRAM instrument, the usual target being below 4 ohm (below 1 ohm for the common earthing at transformer substations). At bransam.ro, an earthing system starts from 900 lei, and the PRAM measurement from 250 lei.

An earthing system is the element that connects the electrical installation to earth in order to protect people from electrocution and equipment from overvoltages. In practice, it gives the fault current a safe path to the ground, so that the circuit breaker or the residual current device (RCD) trips quickly. In this guide we explain step by step how to install an earthing system: which electrodes and strip to use, how they are joined, how to reduce soil resistivity and how to verify everything through PRAM measurement.

What the earthing system is and why it matters

The earthing system (or earthing) is an assembly of buried metal electrodes, connected to each other and linked to the electrical installation through the protective conductor (PE) and the equipotential bonding bar. Its main role is to ensure:

  • protection against electrocution - it disperses dangerous currents into the ground in case of a fault;
  • correct operation of the protections - a good RCD without an efficient earthing system does not provide complete protection;
  • protection against overvoltages - atmospheric discharges, network switching operations, lightning protection;
  • the potential reference for sensitive devices and for photovoltaic equipment.

A properly installed and measured earthing system is also a requirement when connecting to the grid. The distribution operator, Retele Electrice Romania S.A. (formerly E-Distributie Muntenia / Enel, PPC group), may require an earthing verification certificate when energising the electrical connection (bransament).

Materials needed for the earthing system

All buried components must be made of corrosion-resistant materials, usually hot-dip galvanised steel (OL-Zn). Here are the basic elements.

ElementUsual materialIndicative dimensionsRole
Vertical electrodeOL-Zn pipe/profile/angle bar or copperLength 1.5-3 mDisperses the current into the depth
Strip (horizontal electrode)OL-Zn flat bar40x4 mmConnects the electrodes to each other
JointsWelding + clamps/clips-Electrical continuity
Separation pieceTest terminal/plate-Allows PRAM measurement
Connecting conductorCopper or OL-Znas per designConnects the earthing to the PE bar
Soil additivesSalt + bentoniteas requiredReduce resistivity

The number of electrodes and the length of the strip are established according to the soil resistivity and the target resistance value. The drier, sandier or rockier the soil, the more electrodes or a more extensive earthing system are required.

How to install an earthing system step by step

Step 1 - Setting out and digging the trench

The route of the earthing system is established, usually a trench around the foundation or in a line/loop. The laying depth of the strip must be a minimum of 0.8 m, so that the earthing system remains in moist soil and below the frost depth. An earthing system placed too close to the surface has unstable resistance, high in summer and winter.

Step 2 - Driving in the vertical electrodes

The vertical electrodes (OL-Zn pipes or profiles of 1.5-3 m) are driven into the ground at the ends and along the route of the trench, at a distance from one another of at least the length of the electrode (usually 3 m between them). Correct spacing avoids “overlapping” of the influence zones and maintains low resistance. In hard soil, a pointed electrode-stake or drilling can be used.

Step 3 - Laying and welding the OL-Zn strip

The galvanised steel strip (typically 40x4 mm) is placed at the bottom of the trench and connected to each vertical electrode. The joints are made by welding, after which the welded area is given anti-corrosion protection (bitumen/paint), because welding destroys the local galvanising. Poor electrical continuity at the joints is one of the most frequent causes of a “bad” earthing system.

Step 4 - Reducing soil resistivity (salt and bentonite)

For lower dispersion resistance, a layer of salt mixed with bentonite (or commercial bentonite-based products) is added around the electrodes and the strip, and it is moistened. Bentonite retains moisture and maintains electrical contact over the long term. Caution: salt on its own accelerates corrosion, which is why it is used in combination and in moderation.

Step 5 - Backfilling the trench

The trench is covered with soil free of large stones or rubble, in compacted layers, for good contact between the strip and the soil. Filling with dry, draining material (clean gravel) should be avoided, as it increases resistance.

Step 6 - The separation piece and connecting to the bar

At the point where it emerges from the ground, a separation piece (test terminal) is mounted in an accessible box. This allows the earthing system to be disconnected for periodic measurement and verification. From here, the protective conductor runs to the equipotential bonding bar and to the electrical panel.

Step 7 - Measuring the dispersion resistance (PRAM)

After installation, the earthing system must be verified through PRAM measurement (Protection through Relays, Automation and Measurements) with a dedicated instrument. The dispersion resistance is determined and, if it is too high, electrodes or additives are added until the target value is reached. The result is recorded in a verification certificate signed by certified personnel.

What value the earthing system should have

The target value depends on the type of installation and the protections used. Below are usual indicative benchmarks (the exact values are established through the design and the applicable standards):

Type of installationIndicative target resistance
Domestic installation with RCDusually <= 4 ohm
Common earthing at a transformer substation<= 1 ohm
Earthing for lightning protection / LPS<= 10 ohm (as per standard)
Sensitive equipment / photovoltaicas per the manufacturer’s requirements

Remember that an earthing system only “passes” if the measured value meets the requirement, and the measurement must be repeated periodically, because resistance increases over time through corrosion and drying of the soil.

Common mistakes when installing the earthing system

  • Insufficient depth - a strip below 0.8 m leads to high and unstable values.
  • Joints with bolts only, without welding - poor contact, rapid corrosion.
  • Unsuitable material - non-galvanised steel or cross-sections that are too small and rust quickly.
  • Lack of measurement - without a PRAM certificate you do not know whether the earthing system truly protects.
  • Excess salt - it corrodes the electrodes and “eats away” the earthing system within a few years.
  • Distances between electrodes that are too small - they do not reduce resistance proportionally.

Why you should call on an ANRE-certified company

The earthing system seems simple, but the final value depends on the soil, sizing, the quality of the welds and correct measurement. A company certified by ANRE for installation and design, such as SUN WATT SRL (bransam.ro), sizes the earthing system, installs it correctly and issues the PRAM certificate required at grid connection (racordare). We work in Bucharest, Ilfov and Giurgiu and can coordinate the earthing system with the rest of the works: electrical installations, earthing systems and PRAM measurements.

The earthing system is usually one piece of the puzzle of an electrical connection (bransament) or a grid connection for electricity. If you are installing panels, it is also essential for a safe prosumer / photovoltaic grid connection.

Indicative costs

At bransam.ro, an earthing system starts from 900 lei, and the PRAM measurement from 250 lei. The final price depends on the nature of the soil, the number of electrodes and the target value, and is confirmed after assessment. For a quote and to book an appointment, call 0733 097 440 or write to us through the contact page.

Conclusion

A correct earthing system means vertical electrodes driven in deep enough, connected with an OL-Zn strip through welding, soil treated for low resistivity and, most importantly, a PRAM measurement that confirms the target value. Without measurement, there is no guarantee that the installation protects you. Leave the installation and verification to an ANRE-certified team and you get a safe, compliant and documented earthing system.

Frequently asked questions

What depth should the earthing system have?

The strip (the horizontal electrode) is laid at a minimum of 0.8 m, below the frost depth, so that it remains in moist soil and has stable resistance throughout the year. The vertical electrodes are usually 1.5-3 m and are driven into the depth from the bottom of the trench.

What maximum value should the earthing resistance have?

For a domestic installation with a residual current device (RCD), the usual target is below 4 ohm. For the common earthing of transformer substations, below 1 ohm is required, and for lightning protection below 10 ohm. The exact value is established through the design and confirmed through PRAM measurement.

Is PRAM measurement mandatory after installation?

Yes. Only by measuring the dispersion resistance with a PRAM instrument and issuing a verification certificate can it be confirmed that the earthing system meets the target value. The certificate may be required at grid connection and is renewed periodically, because resistance increases over time.

Why are salt and bentonite added to the earthing system?

To lower the soil resistivity around the electrodes and to maintain moisture over the long term. Bentonite retains water and ensures stable electrical contact. Salt is used in moderation and combined with bentonite, because in excess it accelerates corrosion of the electrodes.

How much does an earthing system cost at bransam.ro?

An earthing system starts from 900 lei, and the PRAM measurement from 250 lei. The final price depends on the type of soil, the number of electrodes and the target value. For a quote and to book an appointment in Bucharest, Ilfov or Giurgiu, call 0733 097 440.

Need an electrical connection?

Get a free quote. We handle everything — from paperwork to the pole.

  • ✓ Free assessment & quote
  • ✓ Reply within 24h
  • ✓ ANRE-certified — execution + design
  • ✓ We handle all the paperwork
Call now WhatsApp
Message us on WhatsApp